Portfolio 3 Columns

TSBG Hosting Ltd. own several carrier neutral datacenters, located at diverse locations. All sites are designed and built in accordance with TIA-942 standard and industry best practices. All sites meet or exceed specifications for TIER-3 datacenter.

All buildings have reinforced concrete load bearing frame and brick walls with outer thermal insulation with Expanded polystyrene (EPS) or similar and silicone plaster. Read more about datacenter location selection and building design and construction in our blog How to Select Datacenter Location and Construct the Building

From inside all the walls are finished with two layers of plaster board mounted on galvanised steel frame and inner insulation, made of mineral wool behind the dry walls. The system used is Knauf high performance  plasterboard. You can find more information about Knauf system on www.

Computer room and communications room have heavy duty access floor made of high density chipboard panels. The panels comply with the European Standard EN12825 and are tested in accordance with EN 13501. The top surface of the panel is covered with PVC in grey color. The bottom surface of the panel is supplied with applied layer of aluminium. The panel dimensions are 600 x 600 x 38 mm. The panels are installed on adjustable feet, afixed to the building floor with polyurethane adhesive. The min rise of the floor is 25 cm. When necessary,  additional stringers are used, bolted between the feet . Our prefered supplier of access floor is Jansen. More information can be found here:    https://jansenaccessfloors.com/products/details/high-density-chipboard-panels

The ceiling is finished with suspended plates on exposed grid demountable system. The plates are for clean rooms Class 3 as per ISO 14644 standard. Fire resistance of the ceiling is up to 60 minutes as per BS 476: part 20-23. Our preffered material for suspended ceilings is AMF Thermatex Thermaclean from Knauf. More information and datasheet download can be found here https://www.knaufceilingsolutions.com/en/downloads/.

All the doors to computer room, telecom rooms and power rooms are fire resistant classes T30 (EI2 30), in accordance with EN 1634-1 and aproved according to DIN 4102, 30 min. For easy loading/unloading of racks and equipment and when possible the door height is designed to be 230 cm. More details here https://www.novoferm.com/products/doors-and-frames/fire-resistant-doors/

 

About TSBG Hosting Ltd.

TSBG Hosting Ltd. (TSBG) was founded in 2006 and is incorporated under the laws of the Republic of Bulgaria.

EU VAT tax number: BG175059953

Managing Director: Ivan Shishkov

 

 

 

 

Get In Touch

Address: 8, Racho Dimchev str.

Sofia 1000, Bulgaria

Phone: +359 886 151048

Viber: +359 886 151048

Email: sales@tsbg.eu

Website: www.tsbg.eu

Join Our Community

Sign up to receive email for the latest information.

Search